Accessories

CENTRAL CO

CENTRAL CO

Monoxide detection control box, for ventilation in parking lots

To comply with Royal Decree 2367/1985 and the Technical Building Code, carbon monoxide detection plants have been designed for application in underground car parks, tunnels or other places where dangerous concentrations of CO can accumulate.

The system consists of the installation of a control panel with 1 to 3 zone modules with an indicator display and each module allows the connection of up to 32 detectors connected with 2 wires, with a maximum distance to the last detector of 2 km. The detectors can be distributed over 2,000 m in length and each detector covers a maximum surface area of 200 m2, as defined by current regulations.

Through the optional card FM-TC500 it is possible to control an RFM or RFT series speed regulator, in order to reduce energy consumption and the noise level of the extractors.
These systems involve a significant energy saving.
• Certified system according to UNE 23300/84 standard.
• Certification LOM 09MOGA3054.
• Modular and extensible central control.
• Up to 19,000 m² of management.
• Versions of 1, 2, and 3 zone modules.
• Indication of the concentration per area.
• 2 extraction relay outputs by zone.
• 1 alarm relay output per zone.
• Up to 32 detectors per zone.
• 2 wires connection detectors.
• Mode of operation for low consumption.
• Variable speed ​control option to reduce energy consumption and noise level.
• Option of remote control of the system and integration with energy analysis systems.

Control units FMC-C-501/502/503 Series:
• For 1, 2 or 3 zones depending on the model.
• Supply Voltage: 90-264 V AC.
• Power: 45 W.
• FM-M-509 zone extension module.
• Wiring of the area: 2 wires.
• Maximum distance from the zone line: 2 km with 1.5 mm² cable.
• Number of detectors per zone: 32 detectors.

CO Detector series FM-DP500/FM-D500:
• Wall or ceiling mounted CO Detector according to model.
• Technology: electrochemical cell.
• Lifespan: 10 years.
• Resolution: 1 ppm.
• Reaction time: 10 seconds.
• Storage temperature: -10 ºC to +80 ºC.
• Working area: 200 m² limited by regulation.
• IP degree of protection of FM-D500: Ceiling CO detector. IP20.
• IP degree of protection of FM-DP500: Wall CO detector. IP54.

Control card by inverter FM-TC500 series:
• Module with PWM outputs that allows the extraction motors to be controlled by speed regulators (energy saving).
• Communications module to carry out remote maintenance and remote management actions.
• Open communications protocol for integration with other systems.