TCMP

TCMP

400 ºC/2h centrifugal extractor fans, with forward curved impeller

400 ºC/2h centrifugal single inlet extractor fans for outdoor operation in fire risk zones.

Fan:
• Sheet steel casing.
• Forward curved impeller in galvanised sheet steel.
• Approved in accordance with standard EN 12101-3, with certificate no.: 0370-CPR- 0313.

Motor:
• Class F motors with ball bearings and IP55 protection.
• Motors with IE3 efficiency for powers equal to or greater than 0.75 kW, except single-phase, 2-speed and 8-pole.
• Three-phase 230/400 V 50 Hz (up to 4 kW) and 400/690 V 50 Hz (powers greater than 4 kW).
• Maximum temperature of air to be carried: S1 -25 ºC+ 250 ºC continuous service. S2 300 ºC/2h and 400 ºC/2h service.

Finish:
• Anti-corrosive finish in polyester resin, polymerised at 190 ºC, after degreasing with phosphate-free nanotechnology treatment.

On request:
• Fans with 2 speed motor.
• Belt driven extractor fans.